Debian Codegraph @

src/hardware/ups/socomec/netvision/snmp/mode/battery.pm

raw
1 #
2 # Copyright 2024 Centreon (http://www.centreon.com/)
3 #
4 # Centreon is a full-fledged industry-strength solution that meets
5 # the needs in IT infrastructure and application monitoring for
6 # service performance.
7 #
8 # Licensed under the Apache License, Version 2.0 (the "License");
9 # you may not use this file except in compliance with the License.
10 # You may obtain a copy of the License at
11 #
12 # http://www.apache.org/licenses/LICENSE-2.0
13 #
14 # Unless required by applicable law or agreed to in writing, software
15 # distributed under the License is distributed on an "AS IS" BASIS,
16 # WITHOUT WARRANTIES OR CONDITIONS OF ANY KIND, either express or implied.
17 # See the License for the specific language governing permissions and
18 # limitations under the License.
19 #
20
21 package hardware::ups::socomec::netvision::snmp::mode::battery;
22
23 use base qw(centreon::plugins::templates::counter);
24
25 use strict;
26 use warnings;
27 use centreon::plugins::templates::catalog_functions qw(catalog_status_threshold_ng);
28
29 sub custom_status_output {
30 my ($self, %options) = @_;
31
32 return sprintf('battery status is %s', $self->{result_values}->{status});
33 }
34
35 sub custom_load_output {
36 my ($self, %options) = @_;
37
38 return sprintf(
39 'charge remaining: %s%% (%s minutes remaining)',
40 $self->{result_values}->{charge_remain},
41 $self->{result_values}->{minute_remain}
42 );
43 }
44
45 sub set_counters {
46 my ($self, %options) = @_;
47
48 $self->{maps_counters_type} = [
49 { name => 'global', type => 0, message_separator => ' - ', skipped_code => { -10 => 1 } }
50 ];
51
52 $self->{maps_counters}->{global} = [
53 {
54 label => 'status',
55 type => 2,
56 unknown_default => '%{status} =~ /unknown/i',
57 warning_default => '%{status} =~ /low/i',
58 critical_default => '%{status} =~ /depleted|failure/i',
59 set => {
60 key_values => [ { name => 'status' } ],
61 closure_custom_output => $self->can('custom_status_output'),
62 closure_custom_perfdata => sub { return 0; },
63 closure_custom_threshold_check => \&catalog_status_threshold_ng
64 }
65 },
66 { label => 'charge-remaining', nlabel => 'battery.charge.remaining.percent', set => {
67 key_values => [ { name => 'charge_remain' }, { name => 'minute_remain' } ],
68 closure_custom_output => $self->can('custom_load_output'),
69 perfdatas => [
70 { template => '%s', min => 0, max => 100, unit => '%' }
71 ]
72 }
73 },
74 { label => 'charge-remaining-minutes', nlabel => 'battery.charge.remaining.minutes', display_ok => 0, set => {
75 key_values => [ { name => 'minute_remain', no_value => 'unknown' } ],
76 output_template => 'minutes remaining: %s',
77 perfdatas => [
78 { template => '%s', min => 0 }
79 ]
80 }
81 },
82 { label => 'current', nlabel => 'battery.current.ampere', display_ok => 0, set => {
83 key_values => [ { name => 'current', no_value => 0 } ],
84 output_template => 'current: %s A',
85 perfdatas => [
86 { template => '%s', min => 0, unit => 'A' }
87 ]
88 }
89 },
90 { label => 'voltage', nlabel => 'battery.voltage.volt', display_ok => 0, set => {
91 key_values => [ { name => 'voltage', no_value => 0 } ],
92 output_template => 'voltage: %s V',
93 perfdatas => [
94 { template => '%s', unit => 'V' }
95 ]
96 }
97 },
98 { label => 'temperature', nlabel => 'battery.temperature.celsius', display_ok => 0, set => {
99 key_values => [ { name => 'temperature', no_value => 0 } ],
100 output_template => 'temperature: %s C',
101 perfdatas => [
102 { template => '%s', unit => 'C' }
103 ]
104 }
105 }
106 ];
107 }
108
109 sub new {
110 my ($class, %options) = @_;
111 my $self = $class->SUPER::new(package => __PACKAGE__, %options, force_new_perfdata => 1);
112 bless $self, $class;
113
114 $options{options}->add_options(arguments => {
115 });
116
117 return $self;
118 }
119
120 my $map_status_v6 = {
121 1 => 'unknown', 2 => 'normal', 3 => 'charging', 4 => 'test',
122 5 => 'discharging', 6 => 'low', 7 => 'depleted', 8 => 'failure',
123 9 => 'disconnected'
124 };
125 my $map_status_v5 = {
126 1 => 'unknown', 2 => 'normal', 3 => 'low',
127 4 => 'depleted', 5 => 'discharging',
128 6 => 'failure', 7 => 'upsOff'
129 };
130
131 my $mapping = {
132 netvision5 => {
133 status => { oid => '.1.3.6.1.4.1.4555.1.1.1.1.2.1', map => $map_status_v5 }, # upsBatteryStatus
134 minute_remain => { oid => '.1.3.6.1.4.1.4555.1.1.1.1.2.3' }, # upsEstimatedMinutesRemaining
135 charge_remain => { oid => '.1.3.6.1.4.1.4555.1.1.1.1.2.4' }, # upsEstimatedChargeRemaining
136 voltage => { oid => '.1.3.6.1.4.1.4555.1.1.1.1.2.5' }, # upsBatteryVoltage (dV)
137 temperature => { oid => '.1.3.6.1.4.1.4555.1.1.1.1.2.6' } # upsBatteryTemperature (degrees Centigrade)
138 },
139 netvision6 => {
140 status => { oid => '.1.3.6.1.4.1.4555.1.1.7.1.2.1', map => $map_status_v6 }, # upsBatteryStatus
141 minute_remain => { oid => '.1.3.6.1.4.1.4555.1.1.7.1.2.3' }, # upsEstimatedMinutesRemaining
142 charge_remain => { oid => '.1.3.6.1.4.1.4555.1.1.7.1.2.4' }, # upsEstimatedChargeRemaining
143 voltage => { oid => '.1.3.6.1.4.1.4555.1.1.7.1.2.5' }, # upsBatteryVoltage (dV)
144 temperature => { oid => '.1.3.6.1.4.1.4555.1.1.7.1.2.6' }, # upsBatteryTemperature (degrees Centigrade)
145 current => { oid => '.1.3.6.1.4.1.4555.1.1.7.1.2.8' } # upsBatteryCurrent (dA)
146 }
147 };
148
149 sub manage_selection {
150 my ($self, %options) = @_;
151
152 my $label = 'netvision6';
153 my $snmp_result = $options{snmp}->get_leef(
154 oids => [ map($_->{oid} . '.0', values(%{$mapping->{$label}})) ]
155 );
156 if (!defined($snmp_result->{ $mapping->{netvision6}->{status}->{oid} . '.0' })) {
157 $label = 'netvision5';
158 $snmp_result = $options{snmp}->get_leef(
159 oids => [ map($_->{oid} . '.0', values(%{$mapping->{$label}})) ],
160 nothing_quit => 1
161 );
162 }
163
164 $self->{global} = $options{snmp}->map_instance(mapping => $mapping->{$label}, results => $snmp_result, instance => 0);
165 $self->{global}->{current} = (defined($self->{global}->{current}) && $self->{global}->{current} =~ /\d/ && $self->{global}->{current} != -1 && $self->{global}->{current} != 65535) ?
166 $self->{global}->{current} * 0.1 : 0;
167 $self->{global}->{voltage} = (defined($self->{global}->{voltage}) && $self->{global}->{voltage} =~ /\d/ && $self->{global}->{voltage} != -1 && $self->{global}->{voltage} != 65535) ?
168 $self->{global}->{voltage} * 0.1 : 0;
169 $self->{global}->{temperature} = (defined($self->{global}->{temperature}) && $self->{global}->{temperature} =~ /\d/) ? $self->{global}->{temperature} * 0.1 : 0;
170 $self->{global}->{minute_remain} = (defined($self->{global}->{minute_remain}) && $self->{global}->{minute_remain} =~ /\d/ && $self->{global}->{minute_remain} != -1) ? $self->{global}->{minute_remain} : 'unknown';
171 $self->{global}->{charge_remain} = (defined($self->{global}->{charge_remain}) && $self->{global}->{charge_remain} =~ /\d/) ? $self->{global}->{charge_remain} : undef;
172 }
173
174 1;
175
176 __END__
177
178 =head1 MODE
179
180 Check battery status and charge remaining.
181
182 =over 8
183
184 =item B<--unknown-status>
185
186 Define the conditions to match for the status to be UNKNOWN (default: '%{status} =~ /unknown/i').
187 You can use the following variables: %{status}
188
189 =item B<--warning-status>
190
191 Define the conditions to match for the status to be WARNING (default: '%{status} =~ /low/i').
192 You can use the following variables: %{status}
193
194 =item B<--critical-status>
195
196 Define the conditions to match for the status to be CRITICAL (default: '%{status} =~ /depleted|failure/i').
197 You can use the following variables: %{status}
198
199 =item B<--warning-*> B<--critical-*>
200
201 Thresholds.
202 Can be: 'charge-remaining' (%), 'charge-remaining-minutes',
203 'current' (A), 'voltage' (V), 'temperature' (C).