Power allocator governor tunables |
| 3 |
================================= |
| 4 |
|
| 5 |
Trip points |
| 6 |
----------- |
| 7 |
|
| 8 |
The governor works optimally with the following two passive trip points: |
| 9 |
|
| 10 |
1. "switch on" trip point: temperature above which the governor |
| 11 |
control loop starts operating. This is the first passive trip |
| 12 |
point of the thermal zone. |
| 13 |
|
| 14 |
2. "desired temperature" trip point: it should be higher than the |
| 15 |
"switch on" trip point. This the target temperature the governor |
| 16 |
is controlling for. This is the last passive trip point of the |
| 17 |
thermal zone. |
| 18 |
|
| 19 |
PID Controller |
| 20 |
-------------- |
| 21 |
|
| 22 |
The power allocator governor implements a |
| 23 |
Proportional-Integral-Derivative controller (PID controller) with |
| 24 |
temperature as the control input and power as the controlled output: |
| 25 |
|
| 26 |
P_max = k_p * e + k_i * err_integral + k_d * diff_err + sustainable_power |
| 27 |
|
| 28 |
where |
| 29 |
- e = desired_temperature - current_temperature |
| 30 |
- err_integral is the sum of previous errors |
| 31 |
- diff_err = e - previous_error |
| 32 |
|
| 33 |
It is similar to the one depicted below:: |
| 34 |
|
| 35 |
k_d |
| 36 |
| |
| 37 |
current_temp | |
| 38 |
| v |
| 39 |
| +----------+ +---+ |
| 40 |
| +----->| diff_err |-->| X |------+ |
| 41 |
| | +----------+ +---+ | |
| 42 |
| | | tdp actor |
| 43 |
| | k_i | | get_requested_power() |
| 44 |
| | | | | | | |
| 45 |
| | | | | | | ... |
| 46 |
v | v v v v v |
| 47 |
+---+ | +-------+ +---+ +---+ +---+ +----------+ |
| 48 |
| S |-----+----->| sum e |----->| X |--->| S |-->| S |-->|power | |
| 49 |
+---+ | +-------+ +---+ +---+ +---+ |allocation| |
| 50 |
^ | ^ +----------+ |
| 51 |
| | | | | |
| 52 |
| | +---+ | | | |
| 53 |
| +------->| X |-------------------+ v v |
| 54 |
| +---+ granted performance |
| 55 |
desired_temperature ^ |
| 56 |
| |
| 57 |
| |
| 58 |
k_po/k_pu |
| 59 |
|
| 60 |
Sustainable power |
| 61 |
----------------- |
| 62 |
|
| 63 |
An estimate of the sustainable dissipatable power (in mW) should be |
| 64 |
provided while registering the thermal zone. This estimates the |
| 65 |
sustained power that can be dissipated at the desired control |
| 66 |
temperature. This is the maximum sustained power for allocation at |
| 67 |
the desired maximum temperature. The actual sustained power can vary |
| 68 |
for a number of reasons. The closed loop controller will take care of |
| 69 |
variations such as environmental conditions, and some factors related |
| 70 |
to the speed-grade of the silicon. `sustainable_power` is therefore |
| 71 |
simply an estimate, and may be tuned to affect the aggressiveness of |
| 72 |
the thermal ramp. For reference, the sustainable power of a 4" phone |
| 73 |
is typically 2000mW, while on a 10" tablet is around 4500mW (may vary |
| 74 |
depending on screen size). It is possible to have the power value |
| 75 |
expressed in an abstract scale. The sustained power should be aligned |
| 76 |
to the scale used by the related cooling devices. |
| 77 |
|
| 78 |
If you are using device tree, do add it as a property of the |
| 79 |
thermal-zone. For example:: |
| 80 |
|
| 81 |
thermal-zones { |
| 82 |
soc_thermal { |
| 83 |
polling-delay = <1000>; |
| 84 |
polling-delay-passive = <100>; |
| 85 |
sustainable-power = <2500>; |
| 86 |
... |
| 87 |
|
| 88 |
Instead, if the thermal zone is registered from the platform code, pass a |
| 89 |
`thermal_zone_params` that has a `sustainable_power`. If no |
| 90 |
`thermal_zone_params` were being passed, then something like below |
| 91 |
will suffice:: |
| 92 |
|
| 93 |
static const struct thermal_zone_params tz_params = { |
| 94 |
.sustainable_power = 3500, |
| 95 |
}; |
| 96 |
|
| 97 |
and then pass `tz_params` as the 5th parameter to |
| 98 |
`thermal_zone_device_register()` |
| 99 |
|
| 100 |
k_po and k_pu |
| 101 |
------------- |
| 102 |
|
| 103 |
The implementation of the PID controller in the power allocator |
| 104 |
thermal governor allows the configuration of two proportional term |
| 105 |
constants: `k_po` and `k_pu`. `k_po` is the proportional term |
| 106 |
constant during temperature overshoot periods (current temperature is |
| 107 |
above "desired temperature" trip point). Conversely, `k_pu` is the |
| 108 |
proportional term constant during temperature undershoot periods |
| 109 |
(current temperature below "desired temperature" trip point). |
| 110 |
|
| 111 |
These controls are intended as the primary mechanism for configuring |
| 112 |
the permitted thermal "ramp" of the system. For instance, a lower |
| 113 |
`k_pu` value will provide a slower ramp, at the cost of capping |
| 114 |
available capacity at a low temperature. On the other hand, a high |
| 115 |
value of `k_pu` will result in the governor granting very high power |
| 116 |
while temperature is low, and may lead to temperature overshooting. |
| 117 |
|
| 118 |
The default value for `k_pu` is:: |
| 119 |
|
| 120 |
2 * sustainable_power / (desired_temperature - switch_on_temp) |
| 121 |
|
| 122 |
This means that at `switch_on_temp` the output of the controller's |
| 123 |
proportional term will be 2 * `sustainable_power`. The default value |
| 124 |
for `k_po` is:: |
| 125 |
|
| 126 |
sustainable_power / (desired_temperature - switch_on_temp) |
| 127 |
|
| 128 |
Focusing on the proportional and feed forward values of the PID |
| 129 |
controller equation we have:: |
| 130 |
|
| 131 |
P_max = k_p * e + sustainable_power |
| 132 |
|
| 133 |
The proportional term is proportional to the difference between the |
| 134 |
desired temperature and the current one. When the current temperature |
| 135 |
is the desired one, then the proportional component is zero and |
| 136 |
`P_max` = `sustainable_power`. That is, the system should operate in |
| 137 |
thermal equilibrium under constant load. `sustainable_power` is only |
| 138 |
an estimate, which is the reason for closed-loop control such as this. |
| 139 |
|
| 140 |
Expanding `k_pu` we get:: |
| 141 |
|
| 142 |
P_max = 2 * sustainable_power * (T_set - T) / (T_set - T_on) + |
| 143 |
sustainable_power |
| 144 |
|
| 145 |
where: |
| 146 |
|
| 147 |
- T_set is the desired temperature |
| 148 |
- T is the current temperature |
| 149 |
- T_on is the switch on temperature |
| 150 |
|
| 151 |
When the current temperature is the switch_on temperature, the above |
| 152 |
formula becomes:: |
| 153 |
|
| 154 |
P_max = 2 * sustainable_power * (T_set - T_on) / (T_set - T_on) + |
| 155 |
sustainable_power = 2 * sustainable_power + sustainable_power = |
| 156 |
3 * sustainable_power |
| 157 |
|
| 158 |
Therefore, the proportional term alone linearly decreases power from |
| 159 |
3 * `sustainable_power` to `sustainable_power` as the temperature |
| 160 |
rises from the switch on temperature to the desired temperature. |
| 161 |
|
| 162 |
k_i and integral_cutoff |
| 163 |
----------------------- |
| 164 |
|
| 165 |
`k_i` configures the PID loop's integral term constant. This term |
| 166 |
allows the PID controller to compensate for long term drift and for |
| 167 |
the quantized nature of the output control: cooling devices can't set |
| 168 |
the exact power that the governor requests. When the temperature |
| 169 |
error is below `integral_cutoff`, errors are accumulated in the |
| 170 |
integral term. This term is then multiplied by `k_i` and the result |
| 171 |
added to the output of the controller. Typically `k_i` is set low (1 |
| 172 |
or 2) and `integral_cutoff` is 0. |
| 173 |
|
| 174 |
k_d |
| 175 |
--- |
| 176 |
|
| 177 |
`k_d` configures the PID loop's derivative term constant. It's |
| 178 |
recommended to leave it as the default: 0. |
| 179 |
|
| 180 |
Cooling device power API |
| 181 |
======================== |
| 182 |
|
| 183 |
Cooling devices controlled by this governor must supply the additional |
| 184 |
"power" API in their `cooling_device_ops`. It consists on three ops: |
| 185 |
|
| 186 |
1. :: |
| 187 |
|
| 188 |
int get_requested_power(struct thermal_cooling_device *cdev, |
| 189 |
struct thermal_zone_device *tz, u32 *power); |
| 190 |
|
| 191 |
|
| 192 |
@cdev: |
| 193 |
The `struct thermal_cooling_device` pointer |
| 194 |
@tz: |
| 195 |
thermal zone in which we are currently operating |
| 196 |
@power: |
| 197 |
pointer in which to store the calculated power |
| 198 |
|
| 199 |
`get_requested_power()` calculates the power requested by the device |
| 200 |
in milliwatts and stores it in @power . It should return 0 on |
| 201 |
success, -E* on failure. This is currently used by the power |
| 202 |
allocator governor to calculate how much power to give to each cooling |
| 203 |
device. |
| 204 |
|
| 205 |
2. :: |
| 206 |
|
| 207 |
int state2power(struct thermal_cooling_device *cdev, struct |
| 208 |
thermal_zone_device *tz, unsigned long state, |
| 209 |
u32 *power); |
| 210 |
|
| 211 |
@cdev: |
| 212 |
The `struct thermal_cooling_device` pointer |
| 213 |
@tz: |
| 214 |
thermal zone in which we are currently operating |
| 215 |
@state: |
| 216 |
A cooling device state |
| 217 |
@power: |
| 218 |
pointer in which to store the equivalent power |
| 219 |
|
| 220 |
Convert cooling device state @state into power consumption in |
| 221 |
milliwatts and store it in @power. It should return 0 on success, -E* |
| 222 |
on failure. This is currently used by thermal core to calculate the |
| 223 |
maximum power that an actor can consume. |
| 224 |
|
| 225 |
3. :: |
| 226 |
|
| 227 |
int power2state(struct thermal_cooling_device *cdev, u32 power, |
| 228 |
unsigned long *state); |
| 229 |
|
| 230 |
@cdev: |
| 231 |
The `struct thermal_cooling_device` pointer |
| 232 |
@power: |
| 233 |
power in milliwatts |
| 234 |
@state: |
| 235 |
pointer in which to store the resulting state |
| 236 |
|
| 237 |
Calculate a cooling device state that would make the device consume at |
| 238 |
most @power mW and store it in @state. It should return 0 on success, |
| 239 |
-E* on failure. This is currently used by the thermal core to convert |
| 240 |
a given power set by the power allocator governor to a state that the |
| 241 |
cooling device can set. It is a function because this conversion may |
| 242 |
depend on external factors that may change so this function should the |
| 243 |
best conversion given "current circumstances". |
| 244 |
|
| 245 |
Cooling device weights |
| 246 |
---------------------- |
| 247 |
|
| 248 |
Weights are a mechanism to bias the allocation among cooling |
| 249 |
devices. They express the relative power efficiency of different |
| 250 |
cooling devices. Higher weight can be used to express higher power |
| 251 |
efficiency. Weighting is relative such that if each cooling device |
| 252 |
has a weight of one they are considered equal. This is particularly |
| 253 |
useful in heterogeneous systems where two cooling devices may perform |
| 254 |
the same kind of compute, but with different efficiency. For example, |
| 255 |
a system with two different types of processors. |
| 256 |
|
| 257 |
If the thermal zone is registered using |
| 258 |
`thermal_zone_device_register()` (i.e., platform code), then weights |
| 259 |
are passed as part of the thermal zone's `thermal_bind_parameters`. |
| 260 |
If the platform is registered using device tree, then they are passed |
| 261 |
as the `contribution` property of each map in the `cooling-maps` node. |
| 262 |
|
| 263 |
Limitations of the power allocator governor |
| 264 |
=========================================== |
| 265 |
|
| 266 |
The power allocator governor's PID controller works best if there is a |
| 267 |
periodic tick. If you have a driver that calls |
| 268 |
`thermal_zone_device_update()` (or anything that ends up calling the |
| 269 |
governor's `throttle()` function) repetitively, the governor response |
| 270 |
won't be very good. Note that this is not particular to this |
| 271 |
governor, step-wise will also misbehave if you call its throttle() |
| 272 |
faster than the normal thermal framework tick (due to interrupts for |
| 273 |
example) as it will overreact. |
| 274 |
|
| 275 |
Energy Model requirements |
| 276 |
========================= |
| 277 |
|
| 278 |
Another important thing is the consistent scale of the power values |
| 279 |
provided by the cooling devices. All of the cooling devices in a single |
| 280 |
thermal zone should have power values reported either in milli-Watts |
| 281 |
or scaled to the same 'abstract scale'. |